15.0 KVA ONLINE UPS 3 PHASE INPUT AND 1 PHASE OUTPUT

The AC input of this device operates on 415V +/- 20% three-phase four-wire voltage and 50Hz +/- 10% frequency. The digital display shows DC voltage, AC voltage, frequency, output voltage, and connected load. Audio alarms warn of battery low, overload, overvoltage, and under voltage. The device uses APWN technology with IGBT and has forced air cooling. It supports lead-acid, tubular, and SMF battery types, with a battery voltage of 240 V. The AC output voltage is 230V+/-2% Single Phase, and the frequency is 50Hz +/-0.5Hz, with pure sine wave waveform and better than 98% efficiency. It has various protections against battery low, short circuit, overload trip, mains cut off, phase failure, and abnormal phase sequence. The device is suitable for computers, hospitals, CNC machines, and all types of industrial applications. Optional features include manual/static bypass, power factor correction, remote display/control, software, and SNMP compatibility.

AC INPUT
VOLTAGE
415V +/- 20% Three Phase Four Wires
FREQUENCY 50Hz +/- 10%
DIGITAL DISPLAY
DC VOLTAGE, AC VOLTAGE, FREQUENCY, OUTPUT VOLTAGE & CONNECTED LOAD
AUDIO ALARMS
BATTERY LOW, OVER LOAD, OVER VOLTAGE, UNDER VOLTAGE
TECHNOLOGY APWN TECHNOLOGY WITH IGBT
COOLING FORCED AIR COOLING
BATTERY TYPE LEAD ACID, TUBULAR, SMF
BATTERY VOLTAGE 240 V
AC OUTPUT
VOLTAGE 230V+/-2% Single Phase
FREQUENCY 50Hz +/-0.5Hz
WAVE FORM PURE SINE WAVE
TRANSFER TIME NIL
EFFICIENCY BETTER THAN 98%
TRANSIENT VOLTAGE VARIATION +/- 2%MAX
POWER FACTOR 0.80 LAGGING
OVER LOAD 125% FOR 10 MIN & 150% FOR 1 MIN
STATIC VOLTAGE REGULATION 6% for 50% STEP LOAD CHARGE
DYNAMIC VOLTAGE REGULATION
1%of NORMINAL FOR ALL VARIATIONS OF LINE LOAD 10% to 100% STEP LOAD CHANGE.
WAVE FORM SINUSOIDAL
TOTAL HARMONIC DISTORTION
FOR LINEAR LOADS 2.5% FOR NON LINEAR LOADS 5%
CREST FACTOR 1:3
OPERATING TEMPERATURE
RANGE 0 C to 40 C
RELATIVE HUMIDITY 95% NON CONDENSING
Max. OPERATING ALTITUDE
WITHOUT DERATING 7500ft / 2285m
ACOUSTIC NOISE <60 db
OPTIONAL
MANUAL/STATIC BY PASS PF CORRECTION/REMOTE DISPLAY/CONTROL SOFTWARE/SNMP COMPATIBILITY
PROTECTION
BATTERY LOW, SHORT CURCUIT, OVERLOAD TRIP, MAINS CUT OFF, PHASE FALIURE, ABNORMAL PHASE SEQUENCE.
APPLICATION
COMPUTERS, HOSPITALS, CNC MACHINES AND ALL TYPES OF INDUSTRIAL APPLICATION.